How Many Amps Does a 4-Ton Heat Pump Use?
Plan on about 40 A at 240 V for a 4-ton (48,000 BTU/h) heat pump, or 9,600 VA in the load calculation, until you have the outdoor unit’s nameplate. That’s our deliberately cautious estimate of 10 A per ton: the minimum circuit ampacity (MCA) printed on the label is the real number, and it’s often lower.
In our example homes, a 4-ton heat pump fits on 100 A service and up with gas cooking, drying and water heating, and on 125 A service and up with an electric range, dryer and water heater (NEC® 220.83). Backup heat strips change that quickly.
4-ton heat pump at a glance
- Cooling capacity
- 48,000 BTU/h
- Planning estimate
- 40 A at 240 V
- Load for the calculation
- 9,600 VA, counted at 100% as new HVAC
- Breaker
- No larger than the MOCP on the label
Will a 4-ton heat pump fit on your panel?
The same example homes we use across the site, each adding a 4-ton heat pump, which takes over from the central AC where the home has one. Open any result to see every step of the calculation.
| Service | Example home | Gas appliances | Electric appliances |
|---|---|---|---|
| 60 A | 1,000 ft² | 75 A · over capacity | 110 A · over capacity |
| 100 A | 1,500 ft² | 77 A · fits | 113 A · over capacity |
| 125 A | 1,800 ft² | 79 A · fits | 114 A · tight fit |
| 150 A | 2,200 ft² | 81 A · fits | 116 A · fits |
| 200 A | 2,800 ft² | 84 A · fits | 119 A · fits |
With backup heat strips
Electric strips in the air handler run together with the heat pump on cold days, so the calculation counts them together as heating, at 100%. Only the larger of heating or cooling counts, and with strips that’s heating:
| Heating setup | Load | Amps at 240 V |
|---|---|---|
| 4-ton heat pump alone | 9,600 VA | 40 A |
| + 5 kW strips | 14,600 VA | 61 A |
| + 10 kW strips | 19,600 VA | 82 A |
| + 15 kW strips | 24,600 VA | 103 A |
Ask your installer whether you need strips at all, and what size. A cold-climate model may need smaller strips or none. More in the heat pump amps guide.
What size breaker does a 4-ton heat pump need?
The one its label allows. The breaker can’t be larger than the maximum overcurrent protection (MOCP) printed on the outdoor unit, and the wire must be rated for at least the MCA. Berkeley Lab puts residential heat pumps in a 20 to 60 A breaker range, always a 2-pole breaker on a dedicated 240 V circuit, with a disconnect within sight of the unit. Tonnage alone can’t tell you the exact breaker: two 4-ton models can carry different labels.
Free download
Panel Capacity Worksheet
A printable sheet to map your panel, list your big appliances and ask an electrician the 10 questions that matter before a quote.
Sources
- NFPA 70, National Electrical Code® — free access (NFPA)
- Sizing Electric Service Panels and Utility Infrastructure for Residential Electrification, technical brief (Lawrence Berkeley National Laboratory, 2024)
- Avoiding Electric Panel and Service Upgrades in Home Electrification (Lawrence Berkeley National Laboratory, 2023)