How Many Amps Does a 3.5-Ton Heat Pump Use?

Plan on about 35 A at 240 V for a 3.5-ton (42,000 BTU/h) heat pump, or 8,400 VA in the load calculation, until you have the outdoor unit’s nameplate. That’s our deliberately cautious estimate of 10 A per ton: the minimum circuit ampacity (MCA) printed on the label is the real number, and it’s often lower.

In our example homes, a 3.5-ton heat pump fits on 100 A service and up with gas cooking, drying and water heating, and on 125 A service and up with an electric range, dryer and water heater (NEC® 220.83). Backup heat strips change that quickly.

3.5-ton heat pump at a glance

Cooling capacity
42,000 BTU/h
Planning estimate
35 A at 240 V
Load for the calculation
8,400 VA, counted at 100% as new HVAC
Breaker
No larger than the MOCP on the label

Will a 3.5-ton heat pump fit on your panel?

The same example homes we use across the site, each adding a 3.5-ton heat pump, which takes over from the central AC where the home has one. Open any result to see every step of the calculation.

ServiceExample homeGas appliancesElectric appliances
60 A1,000 ft²70 A · over capacity105 A · over capacity
100 A1,500 ft²72 A · fits108 A · over capacity
125 A1,800 ft²74 A · fits109 A · tight fit
150 A2,200 ft²76 A · fits111 A · fits
200 A2,800 ft²79 A · fits114 A · fits
Check your own home — 2 minutes

With backup heat strips

Electric strips in the air handler run together with the heat pump on cold days, so the calculation counts them together as heating, at 100%. Only the larger of heating or cooling counts, and with strips that’s heating:

Heating setupLoadAmps at 240 V
3.5-ton heat pump alone8,400 VA35 A
+ 5 kW strips13,400 VA56 A
+ 10 kW strips18,400 VA77 A
+ 15 kW strips23,400 VA98 A

Ask your installer whether you need strips at all, and what size. A cold-climate model may need smaller strips or none. More in the heat pump amps guide.

What size breaker does a 3.5-ton heat pump need?

The one its label allows. The breaker can’t be larger than the maximum overcurrent protection (MOCP) printed on the outdoor unit, and the wire must be rated for at least the MCA. Berkeley Lab puts residential heat pumps in a 20 to 60 A breaker range, always a 2-pole breaker on a dedicated 240 V circuit, with a disconnect within sight of the unit. Tonnage alone can’t tell you the exact breaker: two 3.5-ton models can carry different labels.